Outdoor High Voltage Isolation Switch Flexible Rotation Disconnector Switch
Zhejiang, China
Last Login Date:
Aug 24, 2021
Main Products:
Lightning Arrester, Switchgear, Surge Arrester, Insulator, Fuse Cutout, Composite Insulator, Load Switch, Disconnector, Circuit Breaker, Transform
Product Description
Company Info
Basic Info.
Product Description
Dehler Technology Co., Ltd. specializes in producing high and low voltage switchgear, box type substation, cable branch box, outdoor vacuum circuit breaker, isolation switch, grounding switch, load switch and low voltage components and other products.
Products:
Overview:
(H) GW5 outdoor high-voltage isolating switch is used for three-phase AC 50Hz outdoor high-voltage electrical equipment, for the line to be separated under voltage and no load, as well as for the repair of high-voltage busbars, circuit breakers and other electrical equipment and charging The high voltage line is used for electrical isolation and can also be used to open small capacitors or inductor currents. An insulation distance that meets safety requirements is provided when the knife is in the normal opening position. Widely used in 35-110kV substation.
Main structure and characteristics:
1. Each isolation switch monopole consists of a base, two post insulators, a terminal block, left and right contact assemblies, and a grounding knife;
2. The shaft socket is used between the finger and the finger socket, and the copper soft connection is used between the terminal board and the contact rod, so that the main circuit resistance of the product is greatly reduced.
3. The two pillar insulators are installed on the same base in a "V" shape, which has the advantages of small footprint and reduced installation of metal frame;
4. It adopts rolling shaft transmission, which is easy to operate, flexible to rotate, and easy to open and close.
5. Rotate through the bevel gear to ensure that the opening and closing actions of the two columns are consistent;
6. The two pillars have an angle of intersection of 50 degrees and a rotation angle of 90 degrees. After the opening, there is a sufficient amount of insulation isolation fracture to ensure the safety;
7. The operating mechanism drives the base arm and the pull rod to rotate the two post insulators synchronously to realize the opening and closing operation.
8. The product has three modes: ungrounded, single grounded, and double grounded. There is a reliable mechanical interlock between the spindle and the ground to ensure its safety.
9. Equipped with CJ2 automatic operating mechanism or CS-17G manual mechanism, etc., can be equipped with electromagnetic lock. The positioning device on the operating mechanism can ensure that the contact and the static contact are in the correct contact position or the breaking position.
|
| GW4-40.5 | GW4-72.5 | GW4-126 | ||||
Rated voltage | kV | 40.5 | 72.5 | 126 | ||||
Rated current | A | 630 | 1250 | 630 | 1250 | 630 | 1250 | |
4s rated short-time withstand current | kA | 20 | 31.5 | 20 | 31.5 | 20 | 31.5 | |
| kA | 50 | 80 | 50 | 80 | 50 | 80 | |
1min power frequency withstand voltage (RMS) | kV | Ground 95, fracture 110 | Ground 160,fracture 176 | Ground 185,fracture 210 | ||||
Rated lightning impulse withstand voltage (peak) | kV | Ground 185,fracture 215 | Ground 350,fracture 385 | Ground 450,fracture 520 | ||||
Rated frequency | Hz | 50 | 50 | 50 | ||||
Terminal static mechanical load (horizontal vertical / horizontal horizontal / vertical) | N | 750/400/500 | 750/400/500 | 1000/750/1000 | ||||
nsulator mechanical strength | Porcelain pillar | kN | Bending resistance: 4; anti-twist: 2 | Bending resistance: 4;anti-twist:2 | Bending resistance:4;:3 | |||
| Composite pillar |
| Bending resistance:10;anti-twist: 5 | Bending resistance:6;anti-twist: 3 | Bending resistance:12.5;anti-twist: 5 | |||
Post insulator | Porcelain pillar | mm | Class III antifouling 1020mm | Class III antifouling 1830mm | Class III antifouling 3150mm | |||
| Composite pillar |
| Class III antifouling1020mm Class IV antifouling1256mm | Class III antifouling1830mm | Class III antifouling3150mm | |||
Mechanical life |
| 2000 | 2000 | 2000 | ||||
Type I, Type II earthing switch | 2s short-time withstand current | kA | 8,12.5 | 8,20 | 8,12.5 | 8,20 | 8,12.5 | 8,20 |